300S > Signal modules digital
322-5FF00 - Signal modules digital | Digital output modules
Order no. |
322-5FF00 |
Type | SM 322 |
General information |
|
Note | - |
Features | 8 outputs, in groups of 1 AC 120/230 V Output current 2 A Substitute value output (programmable) |
SPEED-Bus | - |
Current consumption/power loss |
|
Current consumption from backplane bus | 100 mA |
Power loss | 8.6 W |
Technical data digital outputs |
|
Number of outputs | 8 |
Cable length, shielded | 1000 m |
Cable length, unshielded | 600 m |
Rated load voltage | AC 120/230 V |
Current consumption from load voltage L+ (without load) | 2 mA |
Total current per group, horizontal configuration, 40°C | 8 A |
Total current per group, horizontal configuration, 60°C | 4 A |
Total current per group, vertical configuration | 4 A |
Output current at signal "1", rated value | 2 A |
Output delay of "0" to "1" | - |
Output delay of "1" to "0" | - |
Minimum load current | - |
Lamp load | 50 W |
Parallel switching of outputs for redundant control of a load | possible |
Parallel switching of outputs for increased power | not possible |
Actuation of digital input | |
Switching frequency with resistive load | max. 10 Hz |
Switching frequency with inductive load | max. 0.5 Hz |
Switching frequency on lamp load | max. 1 Hz |
Internal limitation of inductive shut-off voltage | - |
Short-circuit protection of output | Fuse 3.15 A /250 V, quick response |
Trigger level | 3.15 A |
Number of operating cycle of relay outputs | - |
Switching capacity of contacts | - |
Output data size | 1 Byte |
Status information, alarms, diagnostics |
|
Status display | green LED per channel |
Interrupts | no |
Process alarm | no |
Diagnostic interrupt | no |
Diagnostic functions | no |
Diagnostics information read-out | none |
Supply voltage display | none |
Group error display | red SF LED |
Channel error display | none |
Isolation |
|
Between channels | |
Between channels of groups to | 1 |
Between channels and backplane bus | |
Insulation tested with | AC 1500 V |
Datasizes |
|
Input bytes | 0 |
Output bytes | 1 |
Parameter bytes | 21 |
Diagnostic bytes | 0 |
Housing |
|
Material | PPE |
Mounting | Rail System 300 |
Mechanical data |
|
Dimensions (WxHxD) | 40 mm x 125 mm x 120 mm |
Weight | 330 g |
Environmental conditions |
|
Operating temperature | 0 °C to 60 °C |
Storage temperature | -25 °C to 70 °C |
Certifications |
|
UL certification | yes |
KC certification | yes |