200V > Funktion modules

250-1BA00 - Function modules | Counter modules

Order no.

250-1BA00

TypeFM 250

General information

Note-
Features2/4 channels with 32/16 Bit
DC 24 V or via backplane bus
Free configurable DC 24 V outputs (1 A)
Up to 1 MHz

Current consumption/power loss

Current consumption from backplane bus80 mA
Power loss2.5 W

Technical data digital inputs

Number of inputs6
Cable length, shielded1000 m
Cable length, unshielded600 m
Rated load voltageDC 24 V
Reverse polarity protection of rated load voltage
Current consumption from load voltage L+ (without load)-
Rated value-
Input voltage for signal "0"DC 0...5 V
Input voltage for signal "1"DC 15...28.8 V
Input voltage hysteresis-
Frequency range-
Input resistance2 kΩ
Input current for signal "1"14 mA
Connection of Two-Wire-BEROs possible-
Max. permissible BERO quiescent current-
Input delay of "0" to "1"0.8 µs
Input delay of "1" to "0"0.8 µs
Number of simultaneously utilizable inputs horizontal configuration6
Number of simultaneously utilizable inputs vertical configuration6
Input characteristic curve-
Initial data size10 Byte

Technical data digital outputs

Number of outputs2
Cable length, shielded1000 m
Cable length, unshielded600 m
Rated load voltageDC 24 V
Reverse polarity protection of rated load voltage
Current consumption from load voltage L+ (without load)10 mA
Total current per group, vertical configuration2 A
Output voltage signal "1" at min. currentL+ (-125 mV)
Output voltage signal "1" at max. currentL+ (-0.8 V)
Output current at signal "1", rated value1 A
Output current, permitted range to 40°C-
Output current, permitted range to 60°C-
Output delay of "0" to "1"max. 100 µs
Output delay of "1" to "0"max. 500 µs
Minimum load current-
Lamp load10 W
Parallel switching of outputs for redundant control of a loadnot possible
Parallel switching of outputs for increased powernot possible
Actuation of digital input-
Switching frequency with resistive loadmax. 1000 Hz
Switching frequency with inductive loadmax. 0.5 Hz
Switching frequency on lamp loadmax. 10 Hz
Internal limitation of inductive shut-off voltageL+ (-52 V)
Short-circuit protection of outputyes, electronic
Trigger level3 A
Number of operating cycle of relay outputs-
Switching capacity of contacts-
Output data size10 Byte

Technical data counters

Number of counters2
Counter width1x32 Bit / 2x16 Bit
Maximum input frequency1 MHz
Maximum count frequency1 MHz
Mode incremental encoder
Mode pulse / direction
Mode pulse
Mode frequency counter
Mode period measurement
Gate input available
Latch input available-
Reset input available
Counter output available

Status information, alarms, diagnostics

Status displayyes
Interruptsno
Process alarmno
Diagnostic interruptno
Diagnostic functionsno
Diagnostics information read-outnone
Supply voltage displayyes
Group error displayred LED
Channel error displaynone

Isolation

Between channels-
Between channels of groups to-
Between channels and backplane bus
Between channels and power supply-
Max. potential difference between circuits-
Max. potential difference between inputs (Ucm)-
Max. potential difference between Mana and Mintern (Uiso)-
Max. potential difference between inputs and Mana (Ucm)-
Max. potential difference between inputs and Mintern (Uiso)-
Max. potential difference between Mintern and outputs-
Insulation tested withDC 500 V

Datasizes

Input bytes10
Output bytes10
Parameter bytes4
Diagnostic bytes0

Housing

MaterialPPE / PA 6.6
MountingProfile rail 35 mm

Mechanical data

Dimensions (WxHxD)25.4 mm x 76 mm x 78 mm
Weight230 g

Environmental conditions

Operating temperature0 °C to 60 °C
Storage temperature-25 °C to 70 °C

Certifications

UL certificationyes
KC certification-

Downloads

[Datasheet]
[Manual]