013-CCF0R00 - CPUs | CPUs STEP7 programmierbar, C-Klasse

Order no.

013-CCF0R00

TypeCPU 013C
Module ID-

General information

Note-
FeaturesSPEED7 technology
16 x DI, 12 x DO, 2 x AI, from which are 4 input channels parameterizable for counters and frequency measurement and 2 Output channels for PWM
64 kB work memory
Memory extension (max. 128 kB)
optionell PROFIBUS-DP slave / PtP (switchable)

Technical data power supply

Power supply (rated value)DC 24 V
Power supply (permitted range)DC 20.4...28.8 V
Reverse polarity protection
Current consumption (no-load operation)120 mA
Current consumption (rated value)360 mA
Inrush current3 A
I²t0.1 A²s
Max. current drain at backplane bus1 A
Max. current drain load supply6 A
Power loss7 W

Technical data digital inputs

Number of inputs16
Cable length, shielded1000 m
Cable length, unshielded600 m
Rated load voltageDC 24 V
Reverse polarity protection of rated load voltage
Current consumption from load voltage L+ (without load)25 mA
Rated valueDC 24 V
Input voltage for signal "0"DC 0...5 V
Input voltage for signal "1"DC 15...28.8 V
Input voltage hysteresis-
Frequency range-
Input resistance-
Input current for signal "1"3 mA
Connection of Two-Wire-BEROs possible
Max. permissible BERO quiescent current0.5 mA
Input delay of "0" to "1"3 µs – 15 ms / 0.5 ms – 15 ms
Input delay of "1" to "0"3 µs – 15 ms / 0.5 ms – 15 ms
Number of simultaneously utilizable inputs horizontal configuration16
Number of simultaneously utilizable inputs vertical configuration16
Input characteristic curveIEC 61131-2, type 1
Initial data size16 Bit

Technical data digital outputs

Number of outputs12
Cable length, shielded1000 m
Cable length, unshielded600 m
Rated load voltageDC 24 V
Reverse polarity protection of rated load voltage
Current consumption from load voltage L+ (without load)20 mA
Total current per group, horizontal configuration, 40°C6 A
Total current per group, horizontal configuration, 60°C6 A
Total current per group, vertical configuration6 A
Output voltage signal "1" at min. currentL+ (-0.8 V)
Output voltage signal "1" at max. currentL+ (-0.8 V)
Output current at signal "1", rated value0.5 A
Output current, permitted range to 40°C5 mA to 0.6 A
Output current, permitted range to 60°C5 mA to 0.6 A
Output current at signal "0" max. (residual current)0.5 mA
Output delay of "0" to "1"2 µs / 30 µs
Output delay of "1" to "0"3 µs / 175 µs
Minimum load current-
Lamp load10 W
Parallel switching of outputs for redundant control of a loadnot possible
Parallel switching of outputs for increased powernot possible
Actuation of digital input
Switching frequency with resistive loadmax. 1000 Hz
Switching frequency with inductive loadmax. 0.5 Hz
Switching frequency on lamp loadmax. 10 Hz
Internal limitation of inductive shut-off voltageL+ (-45 V)
Short-circuit protection of outputyes, electronic
Trigger level1 A
Number of operating cycle of relay outputs-
Switching capacity of contacts-
Output data size12 Bit

Technical data analog inputs

Number of inputs2
Cable length, shielded200 m
Rated load voltage-
Reverse polarity protection of rated load voltage-
Current consumption from load voltage L+ (without load)-
Voltage inputs
Min. input resistance (voltage range)100 kΩ
Input voltage ranges0 V ... +10 V
Operational limit of voltage ranges+/-3.5%
Operational limit of voltage ranges with SFU-
Basic error limit voltage ranges+/-3.0%
Basic error limit voltage ranges with SFU-
Destruction limit voltagemax. 30V
Current inputs-
Max. input resistance (current range)-
Input current ranges-
Operational limit of current ranges-
Operational limit of current ranges with SFU-
Basic error limit current ranges-
Radical error limit current ranges with SFU-
Destruction limit current inputs (electrical current)-
Destruction limit current inputs (voltage)-
Resistance inputs-
Resistance ranges-
Operational limit of resistor ranges-
Operational limit of resistor ranges with SFU-
Basic error limit-
Basic error limit with SFU-
Destruction limit resistance inputs-
Resistance thermometer inputs-
Resistance thermometer ranges-
Operational limit of resistance thermometer ranges-
Operational limit of resistance thermometer ranges with SFU-
Basic error limit thermoresistor ranges-
Basic error limit thermoresistor ranges with SFU-
Destruction limit resistance thermometer inputs-
Thermocouple inputs-
Thermocouple ranges-
Operational limit of thermocouple ranges-
Operational limit of thermocouple ranges with SFU-
Basic error limit thermoelement ranges-
Basic error limit thermoelement ranges with SFU-
Destruction limit thermocouple inputs-
Programmable temperature compensation-
External temperature compensation-
Internal temperature compensation-
Technical unit of temperature measurement-
Resolution in bit12
Measurement principlesuccessive approximation
Basic conversion time0.5 ms
Noise suppression for frequency40 dB
Initial data size4 Byte

Technical data analog outputs

Number of outputs-
Cable length, shielded-
Rated load voltage-
Reverse polarity protection of rated load voltage-
Current consumption from load voltage L+ (without load)-
Voltage output short-circuit protection-
Voltage outputs-
Min. load resistance (voltage range)-
Max. capacitive load (current range)-
Max. inductive load (current range)-
Output voltage ranges-
Operational limit of voltage ranges-
Basic error limit voltage ranges with SFU-
Destruction limit against external applied voltage-
Current outputs-
Max. in load resistance (current range)-
Max. inductive load (current range)-
Typ. open circuit voltage current output-
Output current ranges-
Operational limit of current ranges-
Radical error limit current ranges with SFU-
Destruction limit against external applied voltage-
Settling time for ohmic load-
Settling time for capacitive load-
Settling time for inductive load-
Resolution in bit-
Conversion time-
Substitute value can be applied-
Output data size-

Technical data counters

Number of counters4
Counter width32 Bit
Maximum input frequency100 kHz
Maximum count frequency400 kHz
Mode incremental encoder
Mode pulse / direction
Mode pulse
Mode frequency counter
Mode period measurement
Gate input available
Latch input available
Reset input available-
Counter output available

Load and working memory

Load memory, integrated128 KB
Load memory, maximum128 KB
Work memory, integrated64 KB
Work memory, maximal128 KB
Memory divided in 50% program / 50% data
Memory card slotSD/MMC-Card with max. 2 GB

Hardware configuration

Racks, max.5
Modules per rack, max.total max. 64 minus number line extensions
Number of integrated DP master-
Number of DP master via CP-
Operable function modules64
Operable communication modules PtP64
Operable communication modules LAN-

Status information, alarms, diagnostics

Status displayyes
Interruptsyes
Process alarmyes
Diagnostic interruptyes
Diagnostic functionsyes, parameterizable
Diagnostics information read-outpossible
Supply voltage displaygreen LED
Group error displayred SF LED
Channel error displayred LED per group

Isolation

Between channels
Between channels of groups to16
Between channels and backplane bus
Between channels and power supply-
Max. potential difference between circuitsDC 75 V/ AC 50 V
Max. potential difference between inputs (Ucm)-
Max. potential difference between Mana and Mintern (Uiso)-
Max. potential difference between inputs and Mana (Ucm)-
Max. potential difference between inputs and Mintern (Uiso)-
Max. potential difference between Mintern and outputs-
Insulation tested withDC 500 V

Command processing times

Bit instructions, min.0.02 µs
Word instruction, min.0.02 µs
Double integer arithmetic, min.0.02 µs
Floating-point arithmetic, min.0.12 µs

Timers/Counters and their retentive characteristics

Number of S7 counters512
Number of S7 times512

Data range and retentive characteristic

Number of flags8192 Byte
Number of data blocks1024
Max. data blocks size64 KB
Max. local data size per execution level4096 Byte

Blocks

Number of OBs22
Number of FBs1024
Number of FCs1024
Maximum nesting depth per priority class16
Maximum nesting depth additional within an error OB4

Time

Real-time clock buffered
Clock buffered period (min.)30 d
Accuracy (max. deviation per day)10 s
Number of operating hours counter8
Clock synchronization
Synchronization via MPIMaster/Slave
Synchronization via Ethernet (NTP)no

Address areas (I/O)

Input I/O address area2048 Byte
Output I/O address area2048 Byte
Input process image maximal2048 Byte
Output process image maximal2048 Byte
Digital inputs528
Digital outputs524
Digital inputs central528
Digital outputs central524
Integrated digital inputs16
Integrated digital outputs12
Analog inputs514
Analog outputs256
Analog inputs, central514
Analog outputs, central256
Integrated analog inputs2
Integrated analog outputs-
Number of outputs1
Output voltage (typ)L+ (-1.5 V)
Output voltage (rated value)300 mA
Short-circuit protectionyes, electronic
Binding of potentialPower supply of PLC

Communication functions

PG/OP channel
Global data communication
Number of GD circuits, max.8
Size of GD packets, max.54 Byte
S7 basic communication
S7 basic communication, user data per job76 Byte
S7 communication
S7 communication as server
S7 communication as client-
S7 communication, user data per job160 Byte
Number of connections, max.32

PWM data

PWM channels2
PWM time basis1 µs / 0.1 ms / 1 ms
Period length50µs...65.535ms / 0.1...87ms / 1...87ms
Minimum pulse width0...0.5 * Period duration
Type of outputHighside

Functionality Sub-D interfaces

TypeX3
Type of interfaceRS485
ConnectorSub-D, 9-pin, female
Electrically isolated
MPI
MP²I (MPI/RS232)-
DP master-
DP slaveoptional
Point-to-point interface
5V DC Power supplymax. 90mA, isolated
24V DC Power supplymax. 100mA, non-isolated

Type-
Type of interface-
Connector-
Electrically isolated-
MPI-
MP²I (MPI/RS232)-
DP master-
DP slave-
Point-to-point interface-
5V DC Power supply-
24V DC Power supply-

Functionality MPI

Number of connections, max.32
PG/OP channel
Routing
Global data communication
S7 basic communication
S7 communication
S7 communication as server
S7 communication as client-
Transmission speed, min.19.2 kbit/s
Transmission speed, max.12 Mbit/s

Functionality PROFIBUS slave

PG/OP channel
Routing
S7 communication
S7 communication as server
S7 communication as client-
Direct data exchange (slave-to-slave communication)-
DPV1
Transmission speed, min.9.6 kbit/s
Transmission speed, max.12 Mbit/s
Automatic detection of transmission speed
Transfer memory inputs, max.244 Byte
Transfer memory outputs, max.244 Byte
Address areas, max.32
User data per address area, max.32 Byte

Point-to-point communication

PtP communication
Interface isolated
RS232 interface-
RS422 interface-
RS485 interface
ConnectorSub-D, 9-pin, female
Transmission speed, min.150 bit/s
Transmission speed, max.115.5 kbit/s
Cable length, max.500 m

Point-to-point protocol

ASCII protocol
STX/ETX protocol
3964(R) protocol
RK512 protocol-
USS master protocol
Modbus master protocol
Modbus slave protocol
Special protocols-

Functionality RJ45 interfaces

TypeX1/X2
Type of interfaceEthernet 10/100 MBit Switch
Connector2 x RJ45
Electrically isolated
PG/OP channel
Number of connections, max.4
Productive connections-

Type-
Type of interface-
Connector-
Electrically isolated-
PG/OP channel-
Number of connections, max.-
Productive connections-

Housing

MaterialPPE / PPE GF10
MountingProfile rail 35 mm

Mechanical data

Dimensions (WxHxD)147 mm x 100 mm x 83 mm
Weight310 g

Environmental conditions

Operating temperature0 °C to 60 °C
Storage temperature-25 °C to 70 °C

Certifications

UL certificationin preparation
KC certificationin preparation

Additional Links

[CPU Configurator]