100V > Moduli d'interfaccia
151-4PH00 - Interface modules | Fieldbus slave modules with I/Os, DI
Order no. |
151-4PH00 |
Type | SM 151 |
General information |
|
Note | - |
Features | PROFIBUS-DP slave 16 inputs |
Technical data power supply |
|
Power supply (rated value) | DC 24 V |
Power supply (permitted range) | DC 20.4...28.8 V |
Reverse polarity protection | |
Current consumption (no-load operation) | - |
Current consumption (rated value) | 55 mA |
Inrush current | 40 A |
I²t | 0.15 A²s |
Technical data digital inputs |
|
Number of inputs | 16 |
Cable length, shielded | 1000 m |
Cable length, unshielded | 600 m |
Rated load voltage | DC 24 V |
Reverse polarity protection of rated load voltage | - |
Current consumption from load voltage L+ (without load) | - |
Rated value | DC 24 V |
Input voltage for signal "0" | DC 0...5 V |
Input voltage for signal "1" | DC 15...28.8 V |
Input voltage hysteresis | - |
Frequency range | - |
Input resistance | - |
Input current for signal "1" | 7 mA |
Connection of Two-Wire-BEROs possible | |
Max. permissible BERO quiescent current | 1.5 mA |
Input delay of "0" to "1" | 3 ms |
Input delay of "1" to "0" | 3 ms |
Number of simultaneously utilizable inputs horizontal configuration | 16 |
Number of simultaneously utilizable inputs vertical configuration | 16 |
Input characteristic curve | IEC 61131-2, type 1 |
Initial data size | 2 Byte |
Status information, alarms, diagnostics |
|
Status display | green LED per channel |
Interrupts | no |
Process alarm | no |
Diagnostic interrupt | no |
Diagnostic functions | no |
Diagnostics information read-out | possible |
Supply voltage display | yes |
Group error display | red SF LED |
Channel error display | none |
Isolation |
|
Between channels | - |
Between channels of groups to | - |
Between channels and backplane bus | - |
Between channels and power supply | - |
Max. potential difference between circuits | - |
Max. potential difference between inputs (Ucm) | - |
Max. potential difference between Mana and Mintern (Uiso) | - |
Max. potential difference between inputs and Mana (Ucm) | - |
Max. potential difference between inputs and Mintern (Uiso) | - |
Max. potential difference between Mintern and outputs | - |
Insulation tested with | DC 500 V |
Hardware configuration |
|
Racks, max. | - |
Modules per rack, max. | - |
Number of digital modules, max. | - |
Number of analog modules, max. | - |
Communication |
|
Fieldbus | PROFIBUS-DP to EN 50170 |
Type of interface | RS485 |
Connector | Sub-D, 9-pin, female |
Topology | Linear bus with bus termination at both ends |
Electrically isolated | |
Number of participants, max. | 125 |
Node addresses | 1 - 99 |
Transmission speed, min. | 9.6 kbit/s |
Transmission speed, max. | 12 Mbit/s |
Address range inputs, max. | 2 Byte |
Address range outputs, max. | 0 Byte |
Number of TxPDOs, max. | - |
Number of RxPDOs, max. | - |
Datasizes |
|
Input bytes | 1 |
Output bytes | 0 |
Parameter bytes | 7 + 5 |
Diagnostic bytes | 0 |
Housing |
|
Material | PPE / PA 6.6 |
Mounting | Profile rail 35 mm |
Mechanical data |
|
Dimensions (WxHxD) | 101.6 mm x 76 mm x 48 mm |
Weight | 217 g |
Environmental conditions |
|
Operating temperature | 0 °C to 60 °C |
Storage temperature | -25 °C to 70 °C |
Certifications |
|
UL certification | yes |
KC certification | - |