SLIO > Function modules

050-1BA00 - Function modules | Counter modules

Order no.

050-1BA00

TypeFM 050
Module ID08C1 3800

General information

Note-
Features1 Counter 32 Bit (AB)
DC 24 V

Current consumption/power loss

Current consumption from backplane bus75 mA
Power loss1 W

Technical data digital inputs

Number of inputs5
Cable length, shielded100 m
Cable length, unshielded-
Rated load voltageDC 20.4...28.8 V
Reverse polarity protection of rated load voltage-
Current consumption from load voltage L+ (without load)20 mA
Rated valueDC 20.4...28.8 V
Input voltage for signal "0"DC 0...5 V
Input voltage for signal "1"DC 15...28.8 V
Input voltage hysteresis-
Frequency range-
Input resistance-
Input current for signal "1"3 mA
Connection of Two-Wire-BEROs possible
Max. permissible BERO quiescent current0.5 mA
Input delay of "0" to "1"0.8 µs
Input delay of "1" to "0"0.8 µs
Number of simultaneously utilizable inputs horizontal configuration5
Number of simultaneously utilizable inputs vertical configuration5
Input characteristic curveIEC 61131-2, type 1
Initial data size12 Byte

Technical data digital outputs

Number of outputs1
Cable length, shielded100 m
Cable length, unshielded100 m
Rated load voltageDC 20.4...28.8 V
Current consumption from load voltage L+ (without load)-
Output delay of "0" to "1"30 µs
Output delay of "1" to "0"30 µs
Minimum load current-
Lamp load10 W
Parallel switching of outputs for redundant control of a loadnot possible
Parallel switching of outputs for increased powernot possible
Actuation of digital input
Switching frequency with resistive loadmax. 10 kHz
Switching frequency with inductive loadmax. 0.5 Hz
Switching frequency on lamp loadmax. 10 kHz
Internal limitation of inductive shut-off voltageL+ (-52 V)
Short-circuit protection of outputyes, electronic
Trigger level1 A
Number of operating cycle of relay outputs-
Switching capacity of contacts-
Output data size10 Byte

Technical data counters

Number of counters1
Counter width32 Bit
Maximum input frequency100 kHz
Maximum count frequency400 kHz
Mode incremental encoder
Mode pulse / direction
Mode pulse-
Mode frequency counter-
Mode period measurement-
Gate input available
Latch input available
Reset input available
Counter output available

Status information, alarms, diagnostics

Status displayyes
Interruptsyes, parameterizable
Process alarmyes, parameterizable
Diagnostic interruptyes, parameterizable
Diagnostic functionsyes, parameterizable
Diagnostics information read-outpossible
Module stategreen LED
Module error displayred LED
Channel error displaynone

Isolation

Between channels-
Between channels of groups to-
Between channels and backplane bus
Between channels and power supply-
Max. potential difference between circuits-
Max. potential difference between inputs (Ucm)-
Max. potential difference between Mana and Mintern (Uiso)-
Max. potential difference between inputs and Mana (Ucm)-
Max. potential difference between inputs and Mintern (Uiso)-
Max. potential difference between Mintern and outputs-
Insulation tested withDC 500 V

Datasizes

Input bytes12
Output bytes10
Parameter bytes25
Diagnostic bytes20

Housing

MaterialPPE / PPE GF10
MountingProfile rail 35 mm

Mechanical data

Dimensions (WxHxD)12.9 mm x 109 mm x 76.5 mm
Weight60 g

Environmental conditions

Operating temperature0 °C to 60 °C
Storage temperature-25 °C to 70 °C

Certifications

UL certificationyes
KC certificationyes

Downloads

[Datasheet]
[Manual]

[STP]