SLIO > Interface modules

053-1PN00 - Interface modules | Fieldbus slave modules without I/Os

Order no.

053-1PN00

TypeIM 053PN
Module ID-

General information

Note-
FeaturesPROFINET-IO slave
Transfer rate 100Mbit/s
up to 64 peripheral modules

Technical data power supply

Power supply (rated value)DC 24 V
Power supply (permitted range)DC 20.4...28.8 V
Reverse polarity protection
Current consumption (no-load operation)95 mA
Current consumption (rated value)0.95 A
Inrush current3.9 A
I²t0.14 A²s
Max. current drain at backplane bus3 A
Max. current drain load supply10 A
Power loss3 W

Status information, alarms, diagnostics

Status displayyes
Interruptsyes, parameterizable
Process alarmyes, parameterizable
Diagnostic interruptyes, parameterizable
Diagnostic functionsyes, parameterizable
Diagnostics information read-outpossible
Supply voltage displaygreen LED
Service Indicatoryellow LED
Group error displayred SF LED
Channel error displaynone

Hardware configuration

Racks, max.1
Modules per rack, max.64
Number of digital modules, max.64
Number of analog modules, max.64

Communication

FieldbusPROFINET-IO
Type of interfaceEthernet 100 MBit
Connector2 x RJ45
Topology-
Electrically isolated
Number of participants, max.-
Node addresses-
Transmission speed, min.100 Mbit/s
Transmission speed, max.100 Mbit/s
Address range inputs, max.512 Byte
Address range outputs, max.512 Byte
Number of TxPDOs, max.-
Number of RxPDOs, max.-

Housing

MaterialPPE / PPE GF10
MountingProfile rail 35 mm

Mechanical data

Dimensions (WxHxD)48.5 mm x 109 mm x 76.5 mm
Weight155 g

Environmental conditions

Operating temperature0 °C to 60 °C
Storage temperature-25 °C to 70 °C

Certifications

UL certificationyes
KC certificationyes

Downloads

[Datasheet]
[Manual]

[STP]