SLIO > Signal modules analog
031-1PA00 - Signal modules analog | Energiemess-Module
Order no. |
031-1PA00 |
Type | SM 031 |
Module ID | 0882 2880 |
General information |
|
Note | - |
Features | 1/3 phase 230… Resolution measured value |
Current consumption/power loss |
|
Current consumption from backplane bus | 60 mA |
Power loss | 0.9 W |
Rated load voltage | - |
Status information, alarms, diagnostics |
|
Status display | yes |
Interrupts | yes, parameterizable |
Process alarm | no |
Diagnostic interrupt | no |
Diagnostic functions | yes, parameterizable |
Diagnostics information read-out | possible |
Module state | green LED |
Module error display | red LED |
Channel error display | - |
Isolation |
|
Between channels | - |
Insulation tested with | AC 2200 V |
Energy measurement |
|
Number of channels for measuring | 1* 1..3 phases U/I |
Voltage measuring range | 0..300 V each phase |
Coupling voltage measurement | directly |
Current range | - |
Coupling current measurement | Transformer |
Frequency range | 46...64 Hz |
Measurement accuracy | 1 % |
Available measurement | Active energy Temperature Frequency Voltage RMS Current RMS Active power Reactive power Apparent power Cos phi Harmonic voltage RMS Harmonic current RMS |
Adjustable limits | Voltage RMS min/max Current RMS min/max Cos phi min Temperature max. Frequency min/max |
Datasizes |
|
Input bytes | 16 |
Output bytes | 16 |
Parameter bytes | 28 |
Diagnostic bytes | 20 |
Housing |
|
Material | PPE / PPE GF10 |
Mounting | Profile rail 35 mm |
Mechanical data |
|
Dimensions (WxHxD) | 12.9 mm x 109 mm x 76.5 mm |
Weight | 60 g |
Environmental conditions |
|
Operating temperature | 0 °C to 60 °C |
Storage temperature | -25 °C to 70 °C |
Certifications |
|
UL certification | - |
KC certification | - |