314-6CG13 - CPUs | CPUs STEP7 programmable, class C

Order no.

314-6CG13

TypeCPU 314SC/DPM

General information

Note-
FeaturesSPEED7 technology
24 x DI, 16 x DO, 8 x DIO, 4 x AI, 1 x AI Pt100, 2 x AO
256 kB work memory
Memory extension (max. 1 MB)
PROFIBUS-DP master / PtP (switchable)
Also configurable via TIA-Portal
SPEED-Bus-

Technical data power supply

Power supply (rated value)DC 24 V
Power supply (permitted range)DC 20.4...28.8 V
Reverse polarity protection
Current consumption (no-load operation)350 mA
Current consumption (rated value)1 A
Inrush current11 A
I²t0.7 A²s
Max. current drain at backplane bus3 A
Max. current drain load supply-
Power loss14 W

Technical data digital inputs

Number of inputs24
Cable length, shielded1000 m
Cable length, unshielded600 m
Rated load voltageDC 24 V
Reverse polarity protection of rated load voltage
Current consumption from load voltage L+ (without load)70 mA
Rated valueDC 24 V
Input voltage for signal "0"DC 0...5 V
Input voltage for signal "1"DC 15...28.8 V
Input voltage hysteresis-
Frequency range-
Input resistance-
Input current for signal "1"6 mA
Connection of Two-Wire-BEROs possible
Max. permissible BERO quiescent current1.5 mA
Input delay of "0" to "1"0.1 / 0.35 ms
Input delay of "1" to "0"0.1 / 0.35 ms
Number of simultaneously utilizable inputs horizontal configuration24
Number of simultaneously utilizable inputs vertical configuration24
Input characteristic curveIEC 61131-2, type 1
Initial data size3 Byte

Technical data digital outputs

Number of outputs16
Cable length, shielded1000 m
Cable length, unshielded600 m
Rated load voltageDC 24 V
Reverse polarity protection of rated load voltage-
Current consumption from load voltage L+ (without load)100 mA
Total current per group, horizontal configuration, 40°C3 A
Total current per group, horizontal configuration, 60°C2 A
Total current per group, vertical configuration2 A
Output voltage signal "1" at min. currentL+ (-0.8 V)
Output voltage signal "1" at max. currentL+ (-0.8 V)
Output current at signal "1", rated value0.5 A
Output current, permitted range to 40°C5 mA to 0.6 A
Output current, permitted range to 60°C5 mA to 0.6 A
Output current at signal "0" max. (residual current)0.5 mA
Output delay of "0" to "1"100 µs
Output delay of "1" to "0"100 µs
Minimum load current-
Lamp load5 W
Parallel switching of outputs for redundant control of a loadpossible
Parallel switching of outputs for increased powernot possible
Actuation of digital input
Switching frequency with resistive loadmax. 2.5 kHz
Switching frequency with inductive loadmax. 0.5 Hz
Switching frequency on lamp loadmax. 2.5 kHz
Internal limitation of inductive shut-off voltageL+ (-52 V)
Short-circuit protection of outputyes, electronic
Trigger level1 A
Number of operating cycle of relay outputs-
Switching capacity of contacts-
Output data size2 Byte

Technical data analog inputs

Number of inputs5
Cable length, shielded200 m
Rated load voltageDC 24 V
Reverse polarity protection of rated load voltage
Current consumption from load voltage L+ (without load)-
Voltage inputs
Min. input resistance (voltage range)100 kΩ
Input voltage ranges-10 V ... +10 V
0 V ... +10 V
Operational limit of voltage ranges+/-0.3%
Operational limit of voltage ranges with SFU-
Basic error limit voltage ranges+/-0.2%
Basic error limit voltage ranges with SFU-
Destruction limit voltagemax. 30V
Current inputs
Max. input resistance (current range)100 Ω
Input current ranges-20 mA ... +20 mA
0 mA ... +20 mA
+4 mA ... +20 mA
Operational limit of current ranges+/-0.3%
Operational limit of current ranges with SFU-
Basic error limit current ranges+/-0.2%
Radical error limit current ranges with SFU-
Destruction limit current inputs (electrical current)max. 50mA
Destruction limit current inputs (voltage)max. 30V
Resistance inputs
Resistance ranges0 ... 600 Ohm
Operational limit of resistor ranges+/-0.4%
Operational limit of resistor ranges with SFU-
Basic error limit+/-0.2%
Basic error limit with SFU-
Destruction limit resistance inputsmax. 15V
Resistance thermometer inputs-
Resistance thermometer rangesPt100
Operational limit of resistance thermometer ranges+/-0.6%
Operational limit of resistance thermometer ranges with SFU-
Basic error limit thermoresistor ranges+/-0.4%
Basic error limit thermoresistor ranges with SFU-
Destruction limit resistance thermometer inputsmax. 15V
Thermocouple inputs-
Thermocouple ranges-
Operational limit of thermocouple ranges-
Operational limit of thermocouple ranges with SFU-
Basic error limit thermoelement ranges-
Basic error limit thermoelement ranges with SFU-
Destruction limit thermocouple inputs-
Programmable temperature compensation-
External temperature compensation-
Internal temperature compensation-
Technical unit of temperature measurement°C, °F, K
Resolution in bit12
Measurement principlesuccessive approximation
Basic conversion time0.5 ms
Noise suppression for frequency80 dB
Initial data size10 Byte

Technical data analog outputs

Number of outputs2
Cable length, shielded200 m
Rated load voltage-
Reverse polarity protection of rated load voltage-
Current consumption from load voltage L+ (without load)-
Voltage output short-circuit protection
Voltage outputs
Min. load resistance (voltage range)1 kΩ
Max. capacitive load (current range)1 µF
Max. inductive load (current range)25 mA
Output voltage ranges-10 V ... +10 V
0 V ... +10 V
Operational limit of voltage ranges+/-0.2%
Basic error limit voltage ranges with SFU+/-0.1%
Destruction limit against external applied voltagemax. 16V (30V / 10s)
Current outputs
Max. in load resistance (current range)500 Ω
Max. inductive load (current range)10 mH
Typ. open circuit voltage current output15 V
Output current ranges-20 mA ... +20 mA
0 mA ... +20 mA
+4 mA ... +20 mA
Operational limit of current ranges+/-0.3%
Radical error limit current ranges with SFU+/-0.2%
Destruction limit against external applied voltagemax. 16V (30V / 10s)
Settling time for ohmic load0.5 ms
Settling time for capacitive load0.5 ms
Settling time for inductive load0.5 ms
Resolution in bit12
Conversion time1 ms
Substitute value can be appliedno
Output data size4 Byte

Technical data counters

Number of counters4
Counter width32 Bit
Maximum input frequency60 kHz
Maximum count frequency60 kHz
Mode incremental encoder
Mode pulse / direction
Mode pulse
Mode frequency counter
Mode period measurement
Gate input available
Latch input available
Reset input available-
Counter output available

Load and working memory

Load memory, integrated1 MB
Load memory, maximum1 MB
Work memory, integrated256 KB
Work memory, maximal1 MB
Memory divided in 50% program / 50% data
Memory card slotMMC-Card with max. 1 GB

Hardware configuration

Racks, max.4
Modules per rack, max.8
Number of integrated DP master1
Number of DP master via CP4
Operable function modules8
Operable communication modules PtP8
Operable communication modules LAN8

Status information, alarms, diagnostics

Status displayyes
Interruptsyes
Process alarmyes
Diagnostic interruptyes
Diagnostic functionsno
Diagnostics information read-outpossible
Supply voltage displaygreen LED
Group error displayred SF LED
Channel error displayred LED per group

Isolation

Between channels
Between channels of groups to16
Between channels and backplane bus
Between channels and power supply-
Max. potential difference between circuitsDC 75 V/ AC 50 V
Max. potential difference between inputs (Ucm)-
Max. potential difference between Mana and Mintern (Uiso)-
Max. potential difference between inputs and Mana (Ucm)-
Max. potential difference between inputs and Mintern (Uiso)-
Max. potential difference between Mintern and outputs-
Insulation tested withDC 500 V

Command processing times

Bit instructions, min.0.01 µs
Word instruction, min.0.01 µs
Double integer arithmetic, min.0.01 µs
Floating-point arithmetic, min.0.06 µs

Timers/Counters and their retentive characteristics

Number of S7 counters512
Number of S7 times512

Data range and retentive characteristic

Number of flags8192 Byte
Number of data blocks4095
Max. data blocks size64 KB
Max. local data size per execution level510 Byte

Blocks

Number of OBs15
Number of FBs2048
Number of FCs2048
Maximum nesting depth per priority class8
Maximum nesting depth additional within an error OB4

Time

Real-time clock buffered
Clock buffered period (min.)6 w
Accuracy (max. deviation per day)10 s
Number of operating hours counter8
Clock synchronization
Synchronization via MPIMaster/Slave
Synchronization via Ethernet (NTP)no

Address areas (I/O)

Input I/O address area1024 Byte
Output I/O address area1024 Byte
Input process image maximal128 Byte
Output process image maximal128 Byte
Digital inputs7856
Digital outputs7904
Digital inputs central979
Digital outputs central986
Integrated digital inputs24
32
Integrated digital outputs16
24
Analog inputs494
Analog outputs495
Analog inputs, central253
Analog outputs, central250
Integrated analog inputs5
Integrated analog outputs2

Communication functions

PG/OP channel
Global data communication
Number of GD circuits, max.4
Size of GD packets, max.22 Byte
S7 basic communication
S7 basic communication, user data per job76 Byte
S7 communication
S7 communication as server
S7 communication as client-
S7 communication, user data per job160 Byte
Number of connections, max.32

PWM data

PWM channels4
PWM time basis0.1 ms / 1 ms
Period length4...65535 / 1...65535 * time base
Minimum pulse width0...0.5 * Period duration
Type of outputHighside with 1.1kOhm pulldown

Functionality Sub-D interfaces

TypeX2
Type of interfaceRS485
ConnectorSub-D, 9-pin, female
Electrically isolated-
MPI
MP²I (MPI/RS232)-
DP master-
DP slave-
Point-to-point interface
5V DC Power supplymax. 90mA, non-isolated
24V DC Power supplymax. 100mA, non-isolated

TypeX3
Type of interfaceRS485
ConnectorSub-D, 9-pin, female
Electrically isolated
MPI-
MP²I (MPI/RS232)-
DP masteryes
DP slaveyes
Point-to-point interface
5V DC Power supplymax. 90mA, isolated
24V DC Power supplymax. 100mA, non-isolated

Functionality MPI

Number of connections, max.32
PG/OP channel
Routing
Global data communication
S7 basic communication
S7 communication
S7 communication as server
S7 communication as client-
Transmission speed, min.19.2 kbit/s
Transmission speed, max.187.5 kbit/s

Functionality PROFIBUS master

PG/OP channel
Routing
S7 basic communication
S7 communication
S7 communication as server
S7 communication as client-
Activation/deactivation of DP slaves
Direct data exchange (slave-to-slave communication)-
DPV1
Transmission speed, min.9.6 kbit/s
Transmission speed, max.12 Mbit/s
Number of DP slaves, max.32
Address range inputs, max.1 KB
Address range outputs, max.1 KB
User data inputs per slave, max.244 Byte
User data outputs per slave, max.244 Byte

Functionality PROFIBUS slave

PG/OP channel
Routing
S7 communication
S7 communication as server
S7 communication as client-
Direct data exchange (slave-to-slave communication)-
DPV1
Transmission speed, min.9.6 kbit/s
Transmission speed, max.12 Mbit/s
Automatic detection of transmission speed-
Transfer memory inputs, max.244 Byte
Transfer memory outputs, max.244 Byte
Address areas, max.32
User data per address area, max.32 Byte

Point-to-point communication

PtP communication
Interface isolated
RS232 interface-
RS422 interface-
RS485 interface
ConnectorSub-D, 9-pin, female
Transmission speed, min.150 bit/s
Transmission speed, max.115.5 kbit/s
Cable length, max.500 m

Point-to-point protocol

ASCII protocol
STX/ETX protocol
3964(R) protocol
RK512 protocol-
USS master protocol
Modbus master protocol
Modbus slave protocol-
Special protocols-

Functionality RJ45 interfaces

TypeX5
Type of interfaceEthernet 10/100 MBit
ConnectorRJ45
Electrically isolated
PG/OP channel
Number of connections, max.4
Productive connections-

Housing

MaterialPPE
MountingRail System 300

Mechanical data

Dimensions (WxHxD)120 mm x 125 mm x 120 mm
Weight610 g

Environmental conditions

Operating temperature0 °C to 60 °C
Storage temperature-25 °C to 70 °C

Certifications

UL certificationyes
KC certificationyes

Downloads

[Datasheet]