300S > Signal modules analog
334-0KE00 - Signal modules analog | Analog in/output modules
Order no. |
334-0KE00 |
Type | SM 334 |
General information |
|
Note | - |
Features | 4 inputs, 2 outputs Configurable Resistance Voltage 0...10 V |
SPEED-Bus | - |
Current consumption/power loss |
|
Current consumption from backplane bus | 95 mA |
Power loss | 2 W |
Technical data analog inputs |
|
Number of inputs | 4 |
Cable length, shielded | 100 m |
Rated load voltage | DC 24 V |
Reverse polarity protection of rated load voltage | - |
Current consumption from load voltage L+ (without load) | 40 mA |
Voltage inputs | |
Min. input resistance (voltage range) | 100 kΩ |
Input voltage ranges | 0 V ... +10 V |
Operational limit of voltage ranges | +/-0.7% |
Operational limit of voltage ranges with SFU | - |
Basic error limit voltage ranges | +/-0.5% |
Basic error limit voltage ranges with SFU | - |
Destruction limit voltage | max. 30V |
Current inputs | - |
Max. input resistance (current range) | - |
Input current ranges | - |
Operational limit of current ranges | - |
Operational limit of current ranges with SFU | - |
Basic error limit current ranges | - |
Radical error limit current ranges with SFU | - |
Destruction limit current inputs (electrical current) | - |
Destruction limit current inputs (voltage) | - |
Resistance inputs | |
Resistance ranges | 10000 Ohm |
Operational limit of resistor ranges | +/-3.5% |
Operational limit of resistor ranges with SFU | - |
Basic error limit | +/-2.8% |
Basic error limit with SFU | - |
Destruction limit resistance inputs | max. 25V |
Resistance thermometer inputs | |
Resistance thermometer ranges | Pt100 |
Operational limit of resistance thermometer ranges | +/-1.0% |
Operational limit of resistance thermometer ranges with SFU | - |
Basic error limit thermoresistor ranges | +/-0.8% |
Basic error limit thermoresistor ranges with SFU | - |
Destruction limit resistance thermometer inputs | max. 25V |
Thermocouple inputs | - |
Thermocouple ranges | - |
Operational limit of thermocouple ranges | - |
Operational limit of thermocouple ranges with SFU | - |
Basic error limit thermoelement ranges | - |
Basic error limit thermoelement ranges with SFU | - |
Destruction limit thermocouple inputs | - |
Programmable temperature compensation | - |
External temperature compensation | - |
Internal temperature compensation | - |
Temperature error internal compensation | - |
Technical unit of temperature measurement | °C |
Resolution in bit | 12 |
Measurement principle | Sigma-Delta |
Basic conversion time | 350 ms |
Noise suppression for frequency | 50 Hz/60 Hz |
Initial data size | 8 Byte |
Technical data analog outputs |
|
Number of outputs | 2 |
Cable length, shielded | 100 m |
Rated load voltage | DC 24 V |
Reverse polarity protection of rated load voltage | |
Current consumption from load voltage L+ (without load) | 40 mA |
Voltage output short-circuit protection | |
Voltage outputs | |
Min. load resistance (voltage range) | 1 kΩ |
Max. capacitive load (current range) | 1 µF |
Max. inductive load (current range) | 25 mA |
Output voltage ranges | 0 V ... +10 V |
Operational limit of voltage ranges | +/-1% |
Basic error limit voltage ranges | +/-0.8% |
Destruction limit against external applied voltage | max. 16V (30V / 10s) |
Current outputs | - |
Max. in load resistance (current range) | - |
Max. inductive load (current range) | - |
Typ. open circuit voltage current output | - |
Output current ranges | - |
Operational limit of current ranges | - |
Basic error limit current ranges | - |
Destruction limit against external applied voltage | - |
Settling time for ohmic load | 0.8 ms |
Settling time for capacitive load | 0.8 ms |
Settling time for inductive load | 0.3 ms |
Resolution in bit | 12 |
Conversion time | 0.5 ms per channel |
Substitute value can be applied | - |
Output data size | 4 Byte |
Status information, alarms, diagnostics |
|
Status display | none |
Interrupts | no |
Process alarm | no |
Diagnostic interrupt | no |
Diagnostic functions | no |
Diagnostics information read-out | none |
Supply voltage display | none |
Group error display | none |
Channel error display | none |
Isolation |
|
Between channels | - |
Between channels of groups to | - |
Between channels and backplane bus | |
Between channels and power supply | |
Max. potential difference between circuits | - |
Max. potential difference between inputs (Ucm) | DC 1 V |
Max. potential difference between Mana and Mintern (Uiso) | DC 75 V/ AC 50 V |
Max. potential difference between inputs and Mana (Ucm) | DC 1 V |
Max. potential difference between inputs and Mintern (Uiso) | - |
Max. potential difference between Mintern and outputs | - |
Insulation tested with | DC 500 V |
Datasizes |
|
Input bytes | 8 |
Output bytes | 4 |
Parameter bytes | 21 |
Diagnostic bytes | 0 |
Housing |
|
Material | PPE |
Mounting | Rail System 300 |
Mechanical data |
|
Dimensions (WxHxD) | 40 mm x 125 mm x 120 mm |
Weight | 210 g |
Environmental conditions |
|
Operating temperature | 0 °C to 60 °C |
Storage temperature | -25 °C to 70 °C |
Certifications |
|
UL certification | yes |
KC certification | yes |