300S > Signal modules analog
332-5HD01 - Signal modules analog | Analog output modules
Order no. |
332-5HD01 |
Type | SM 332 |
General information |
|
Note | - |
Features | 4 outputs Configurable Voltage, current |
SPEED-Bus | - |
Current consumption/power loss |
|
Current consumption from backplane bus | 125 mA |
Power loss | 3.5 W |
Technical data analog outputs |
|
Number of outputs | 4 |
Cable length, shielded | - |
Rated load voltage | DC 24 V |
Reverse polarity protection of rated load voltage | - |
Current consumption from load voltage L+ (without load) | 115 mA |
Voltage output short-circuit protection | |
Voltage outputs | |
Min. load resistance (voltage range) | 1 kΩ |
Max. capacitive load (current range) | 1 µF |
Max. inductive load (current range) | 30 mA |
Output voltage ranges | -10 V ... +10 V 0 V ... +10 V +1 V ... +5 V |
Operational limit of voltage ranges | +/-0.2% ... +/-0.8% |
Basic error limit voltage ranges | +/-0.1% ... +/-0.5% |
Destruction limit against external applied voltage | max. 16V (30V / 10s) |
Current outputs | |
Max. in load resistance (current range) | 500 Ω |
Max. inductive load (current range) | 10 mH |
Typ. open circuit voltage current output | - |
Output current ranges | -20 mA ... +20 mA 0 mA ... +20 mA +4 mA ... +20 mA |
Operational limit of current ranges | +/-0.3% ... +/-0.8% |
Basic error limit current ranges | +/-0.2% ... +/-0.5% |
Destruction limit against external applied voltage | max. 16V (30V / 10s) |
Settling time for ohmic load | 0.2 ms |
Settling time for capacitive load | 1 ms |
Settling time for inductive load | 1 ms |
Resolution in bit | 13 |
Conversion time | 1 ms all channels |
Substitute value can be applied | yes |
Output data size | 8 Byte |
Status information, alarms, diagnostics |
|
Status display | green LED per channel |
Interrupts | yes |
Process alarm | no |
Diagnostic interrupt | yes, parameterizable |
Diagnostic functions | yes |
Diagnostics information read-out | possible |
Supply voltage display | none |
Group error display | red SF LED |
Channel error display | red LED per channel |
Isolation |
|
Between channels | - |
Between channels of groups to | - |
Between channels and backplane bus | |
Between channels and power supply | |
Max. potential difference between circuits | - |
Max. potential difference between inputs (Ucm) | - |
Max. potential difference between Mana and Mintern (Uiso) | DC 75 V/ AC 50 V |
Max. potential difference between inputs and Mana (Ucm) | - |
Max. potential difference between inputs and Mintern (Uiso) | - |
Max. potential difference between Mintern and outputs | - |
Insulation tested with | DC 500 V |
Datasizes |
|
Input bytes | 0 |
Output bytes | 8 |
Parameter bytes | 21 |
Diagnostic bytes | 16 |
Housing |
|
Material | PPE |
Mounting | Rail System 300 |
Mechanical data |
|
Dimensions (WxHxD) | 40 mm x 125 mm x 120 mm |
Weight | 230 g |
Environmental conditions |
|
Operating temperature | 0 °C to 60 °C |
Storage temperature | -25 °C to 70 °C |
Certifications |
|
UL certification | yes |
KC certification | yes |