300S > Signal modules analog

334-0KE00 - Signal modules analog | Analog in/output modules

Order no.

334-0KE00

TypeSM 334

General information

Note-
Features4 inputs, 2 outputs
Configurable
Resistance
Voltage 0...10 V
SPEED-Bus-

Current consumption/power loss

Current consumption from backplane bus95 mA
Power loss2 W

Technical data analog inputs

Number of inputs4
Cable length, shielded100 m
Rated load voltageDC 24 V
Reverse polarity protection of rated load voltage-
Current consumption from load voltage L+ (without load)40 mA
Voltage inputs
Min. input resistance (voltage range)100 kΩ
Input voltage ranges0 V ... +10 V
Operational limit of voltage ranges+/-0.7%
Operational limit of voltage ranges with SFU-
Basic error limit voltage ranges+/-0.5%
Basic error limit voltage ranges with SFU-
Destruction limit voltagemax. 30V
Current inputs-
Max. input resistance (current range)-
Input current ranges-
Operational limit of current ranges-
Operational limit of current ranges with SFU-
Basic error limit current ranges-
Radical error limit current ranges with SFU-
Destruction limit current inputs (electrical current)-
Destruction limit current inputs (voltage)-
Resistance inputs
Resistance ranges10000 Ohm
Operational limit of resistor ranges+/-3.5%
Operational limit of resistor ranges with SFU-
Basic error limit+/-2.8%
Basic error limit with SFU-
Destruction limit resistance inputsmax. 25V
Resistance thermometer inputs
Resistance thermometer rangesPt100
Operational limit of resistance thermometer ranges+/-1.0%
Operational limit of resistance thermometer ranges with SFU-
Basic error limit thermoresistor ranges+/-0.8%
Basic error limit thermoresistor ranges with SFU-
Destruction limit resistance thermometer inputsmax. 25V
Thermocouple inputs-
Thermocouple ranges-
Operational limit of thermocouple ranges-
Operational limit of thermocouple ranges with SFU-
Basic error limit thermoelement ranges-
Basic error limit thermoelement ranges with SFU-
Destruction limit thermocouple inputs-
Programmable temperature compensation-
External temperature compensation-
Internal temperature compensation-
Temperature error internal compensation-
Technical unit of temperature measurement°C
Resolution in bit12
Measurement principleSigma-Delta
Basic conversion time350 ms
Noise suppression for frequency50 Hz/60 Hz
Initial data size8 Byte

Technical data analog outputs

Number of outputs2
Cable length, shielded100 m
Rated load voltageDC 24 V
Reverse polarity protection of rated load voltage
Current consumption from load voltage L+ (without load)40 mA
Voltage output short-circuit protection
Voltage outputs
Min. load resistance (voltage range)1 kΩ
Max. capacitive load (current range)1 µF
Max. inductive load (current range)25 mA
Output voltage ranges0 V ... +10 V
Operational limit of voltage ranges+/-1%
Basic error limit voltage ranges+/-0.8%
Destruction limit against external applied voltagemax. 16V (30V / 10s)
Current outputs-
Max. in load resistance (current range)-
Max. inductive load (current range)-
Typ. open circuit voltage current output-
Output current ranges-
Operational limit of current ranges-
Basic error limit current ranges-
Destruction limit against external applied voltage-
Settling time for ohmic load0.8 ms
Settling time for capacitive load0.8 ms
Settling time for inductive load0.3 ms
Resolution in bit12
Conversion time0.5 ms per channel
Substitute value can be applied-
Output data size4 Byte

Status information, alarms, diagnostics

Status displaynone
Interruptsno
Process alarmno
Diagnostic interruptno
Diagnostic functionsno
Diagnostics information read-outnone
Supply voltage displaynone
Group error displaynone
Channel error displaynone

Isolation

Between channels-
Between channels of groups to-
Between channels and backplane bus
Between channels and power supply
Max. potential difference between circuits-
Max. potential difference between inputs (Ucm)DC 1 V
Max. potential difference between Mana and Mintern (Uiso)DC 75 V/ AC 50 V
Max. potential difference between inputs and Mana (Ucm)DC 1 V
Max. potential difference between inputs and Mintern (Uiso)-
Max. potential difference between Mintern and outputs-
Insulation tested withDC 500 V

Datasizes

Input bytes8
Output bytes4
Parameter bytes21
Diagnostic bytes0

Housing

MaterialPPE
MountingRail System 300

Mechanical data

Dimensions (WxHxD)40 mm x 125 mm x 120 mm
Weight210 g

Environmental conditions

Operating temperature0 °C to 60 °C
Storage temperature-25 °C to 70 °C

Certifications

UL certificationyes
KC certificationyes

Downloads

[Datasheet]
[Manual]