300S > Signal modules analog

331-7KF01 - Signal modules analog | Analog input modules

Order no.

331-7KF01

TypeSM 331

General information

Note-
Features8 inputs, in 4 groups
Voltage, current
Resistance
Resitance thermometer
Thermocouples
SPEED-Bus-

Current consumption/power loss

Current consumption from backplane bus95 mA
Power loss3 W

Technical data analog inputs

Number of inputs8
Cable length, shielded50 m
Rated load voltageDC 24 V
Current consumption from load voltage L+ (without load)100 mA
Voltage inputs
Min. input resistance (voltage range)100 kΩ
Input voltage ranges-80 mV ... +80 mV
-250 mV ... +250 mV
-500 mV ... +500 mV
-1 V ... +1 V
-2.5 V ... +2.5 V
-5 V ... +5 V
+1 V ... +5 V
-10 V ... +10 V
Operational limit of voltage ranges+/-0.6% ... +/-1.0%
Operational limit of voltage ranges with SFU-
Basic error limit voltage ranges+/-0.4% ... +/-0.7%
Basic error limit voltage ranges with SFU-
Destruction limit voltagemax. 15V
Current inputs
Max. input resistance (current range)85 Ω
Input current ranges-3.2 mA ... +3.2 mA
-10 mA ... +10 mA
-20 mA ... +20 mA
0 mA ... +20 mA
+4 mA ... +20 mA
Operational limit of current ranges+/-0.7%
Operational limit of current ranges with SFU-
Grundfehlergrenze Strombereiche+/-0.5%
Radical error limit current ranges with SFU-
Destruction limit current inputs (electrical current)max. 40mA
Destruction limit current inputs (voltage)max. 15V
Resistance inputs
Resistance ranges0 ... 150 Ohm
0 ... 300 Ohm
0 ... 600 Ohm
Operational limit of resistor ranges+/-0.7%
Operational limit of resistor ranges with SFU-
Basic error limit+/-0.5%
Basic error limit with SFU-
Destruction limit resistance inputsmax. 15V
Resistance thermometer inputs
Resistance thermometer rangesPt100
Ni100
Operational limit of resistance thermometer ranges+/-0.7% ... +/-0.8%
Operational limit of resistance thermometer ranges with SFU-
Basic error limit thermoresistor ranges+/-0.5% ... +/-0.6%
Basic error limit thermoresistor ranges with SFU-
Destruction limit resistance thermometer inputsmax. 15V
Thermocouple inputs
Thermocouple rangestype J
type R
type K
type N
type L
type E
type T
type S
type B
type C
Operational limit of thermocouple ranges+/-1.3% ... +/-2.0%
Operational limit of thermocouple ranges with SFU-
Basic error limit thermoelement ranges+/-0.7% ... +/-1.0%
Basic error limit thermoelement ranges with SFU-
Destruction limit thermocouple inputsmax. 15V
Programmable temperature compensation
External temperature compensation
Internal temperature compensation
Temperature error internal compensation3 K
Technical unit of temperature measurement°C
Resolution in bit14
Measurement principleSigma-Delta
Basic conversion time4 ms/18 ms/22 ms/68 ms / channel
Noise suppression for frequency1300 Hz/190 Hz/150 Hz/50 Hz + 60 Hz
Initial data size16 Byte

Status information, alarms, diagnostics

Status displaynone
Interruptsyes
Process alarmyes, parameterizable
Diagnostic interruptyes, parameterizable
Diagnostic functionsyes
Diagnostics information read-outpossible
Supply voltage displaynone
Group error displayred SF LED
Channel error displayred LED per channel

Isolation

Between channels-
Between channels of groups to-
Between channels and backplane bus
Between channels and power supply
Max. potential difference between circuits-
Max. potential difference between inputs (Ucm)DC 3 V
Max. potential difference between Mana and Mintern (Uiso)DC 75 V/ AC 50 V
Max. potential difference between inputs and Mana (Ucm)DC 3 V
Max. potential difference between inputs and Mintern (Uiso)-
Max. potential difference between Mintern and outputs-
Insulation tested withDC 500 V

Datasizes

Input bytes16
Output bytes0
Parameter bytes21
Diagnostic bytes16

Housing

MaterialPPE
MountingRail System 300

Mechanical data

Dimensions (WxHxD)40 mm x 125 mm x 120 mm
Weight240 g

Environmental conditions

Operating temperature0 °C to 60 °C
Storage temperature-25 °C to 70 °C

Certifications

UL certificationyes
KC certificationyes

Downloads

[Datasheet]
[Manual]