238-2BC00 - Signal modules analog | Combination modules

Order no.

238-2BC00

TypeSM 238C, Digital In-/Output, Counter, Analog In-/Output

General information

Note-
Features16 (12) digital inputs
0 (4) digital outputs
max. 3 counter
4 analog inputs
2 analog outputs

Current consumption/power loss

Current consumption from backplane bus280 mA
Power loss5.5 W

Technical data digital inputs

Number of inputs16
Cable length, shielded1000 m
Cable length, unshielded600 m
Rated load voltage-
Current consumption from load voltage L+ (without load)-
Rated valueDC 20.4...28.8 V
Input voltage for signal "0"DC 0...5 V
Input voltage for signal "1"DC 15...28.8 V
Input voltage hysteresis-
Frequency range-
Input resistance-
Input current for signal "1"7 mA
Connection of Two-Wire-BEROs possible
Max. permissible BERO quiescent current1.5 mA
Input delay of "0" to "1"3 ms
Input delay of "1" to "0"3 ms
Number of simultaneously utilizable inputs horizontal configuration16
Number of simultaneously utilizable inputs vertical configuration16
Input characteristic curveIEC 61131-2, type 1
Initial data size16 Byte

Technical data digital outputs

Number of outputs4
Cable length, shielded1000 m
Cable length, unshielded600 m
Rated load voltageDC 20.4...28.8 V
Reverse polarity protection of rated load voltage-
Current consumption from load voltage L+ (without load)20 mA
Total current per group, horizontal configuration, 40°C4 A
Total current per group, horizontal configuration, 60°C2 A
Total current per group, vertical configuration4 A
Output voltage signal "1" at min. currentL+ (-125 mV)
Output voltage signal "1" at max. currentL+ (-0.8 V)
Output current at signal "1", rated value1 A
Output delay of "0" to "1"150 µs
Output delay of "1" to "0"100 µs
Minimum load current-
Lamp load5 W
Parallel switching of outputs for redundant control of a loadnot possible
Parallel switching of outputs for increased powernot possible
Actuation of digital input
Switching frequency with resistive loadmax. 1000 Hz
Switching frequency with inductive loadmax. 0.5 Hz
Switching frequency on lamp loadmax. 10 Hz
Internal limitation of inductive shut-off voltageL+ (-52 V)
Short-circuit protection of outputyes, electronic
Trigger level1.5 A
Number of operating cycle of relay outputs-
Switching capacity of contacts-
Output data size16 Byte

Technical data analog inputs

Number of inputs4
Cable length, shielded200 m
Rated load voltageDC 24 V
Reverse polarity protection of rated load voltage
Current consumption from load voltage L+ (without load)70 mA
Voltage inputs
Min. input resistance (voltage range)120 kΩ
Input voltage ranges+1 V ... +5 V
0 V ... +10 V
-10 V ... +10 V
-400 mV ... +400 mV
-4 V ... +4 V
Operational limit of voltage ranges+/-0.3% ... +/-0.7%
Operational limit of voltage ranges with SFU-
Basic error limit voltage ranges with SFU+/-0.2% ... +/-0.5%
Basic error limit voltage ranges with SFU-
Destruction limit voltagemax. 15V
Current inputs
Max. input resistance (current range)90 Ω
Input current ranges+4 mA ... +20 mA
0 mA ... +20 mA
-20 mA ... +20 mA
Operational limit of current ranges+/-0.3% ... +/-0.8%
Operational limit of current ranges with SFU-
Basic error limit current ranges+/-0.2% ... +/-0.5%
Radical error limit current ranges with SFU-
Destruction limit current inputs (electrical current)max. 50mA
Destruction limit current inputs (voltage)max. 15V
Resistance inputs
Resistance ranges0 ... 600 Ohm
0 ... 3000 Ohm
Operational limit of resistor ranges+/-0.4%
Operational limit of resistor ranges with SFU-
Basic error limit+/-0.2%
Basic error limit with SFU-
Destruction limit resistance inputsmax. 15V
Resistance thermometer inputs
Resistance thermometer rangesPt100
Pt1000
Ni100
Ni1000
Operational limit of resistance thermometer ranges+/-0.4% ... +/-1.0%
Operational limit of resistance thermometer ranges with SFU-
Basic error limit thermoresistor ranges+/-0.2% ... +/-0.5%
Basic error limit thermoresistor ranges with SFU-
Destruction limit resistance thermometer inputsmax. 15V
Thermocouple inputs-
Thermocouple ranges-
Operational limit of thermocouple ranges-
Operational limit of thermocouple ranges with SFU-
Basic error limit thermoelement ranges-
Basic error limit thermoresistor ranges with SFU-
Destruction limit thermocouple inputs-
Programmable temperature compensation-
External temperature compensation-
Internal temperature compensation-
Temperature error internal compensation-
Technical unit of temperature measurement°C
Resolution in bit16
Measurement principleSigma-Delta
Basic conversion time7 ms - 272 ms
Noise suppression for frequency50 Hz and 60 Hz
Initial data size8 Byte

Technical data analog outputs

Number of outputs2
Cable length, shielded200 m
Rated load voltageDC 24 V
Reverse polarity protection of rated load voltage
Current consumption from load voltage L+ (without load)70 mA
Voltage output short-circuit protection
Voltage outputs
Min. load resistance (voltage range)1 kΩ
Max. capacitive load (current range)1 µF
Max. inductive load (current range)30 mA
Output voltage ranges-10 V ... +10 V
+1 V ... +5 V
0 V ... +10 V
Operational limit of voltage ranges+/-0.4% ... +/-0.8%
Basic error limit voltage ranges with SFU+/-0.2% ... +/-0.4%
Destruction limit against external applied voltagemax. 15V
Current outputs
Max. in load resistance (current range)500 Ω
Max. inductive load (current range)10 mH
Typ. open circuit voltage current output13 V
Output current ranges-20 mA ... +20 mA
0 mA ... +20 mA
0 mA ... +20 mA
Operational limit of current ranges+/-0.3% ... +/-0.8%
Radical error limit current ranges with SFU+/-0.2% ... +/-0.5%
max. 15V
Settling time for ohmic load0.3 ms
Settling time for capacitive load1 ms
Settling time for inductive load0.5 ms
Resolution in bit12
Conversion time1.50 ms
Substitute value can be appliedyes
Output data size4 Byte

Status information, alarms, diagnostics

Status displayyes
Interruptsyes
Process alarmyes, parameterizable
Diagnostic interruptyes, parameterizable
Diagnostic functionsyes
Diagnostics information read-outpossible
Supply voltage displaygreen LED per group
Group error displayred SF LED
Channel error displaynone

Isolation

Between channels-
Between channels of groups to-
Between channels and backplane bus
Between channels and power supply
Max. potential difference between circuits-
Max. potential difference between inputs (Ucm)DC 4 V
Max. potential difference between Mana and Mintern (Uiso)-
Max. potential difference between inputs and Mana (Ucm)-
Max. potential difference between inputs and Mintern (Uiso)DC 75 V/ AC 50 V
Max. potential difference between Mintern and outputs-
Insulation tested withDC 500 V

Datasizes

Input bytes8 + 16
Output bytes4 + 16
Parameter bytes18 + 71
Diagnostic bytes12 + 12

Housing

MaterialPPE / PA 6.6
MountingProfile rail 35 mm

Mechanical data

Dimensions (WxHxD)50.8 mm x 76 mm x 88 mm
Weight150 g

Environmental conditions

Operating temperature0 °C to 60 °C
Storage temperature-25 °C to 70 °C

Certifications

UL certificationyes
KC certification-

Downloads