234-1BD60 - Signal modules analog | Analog in/output modules

Order no.

234-1BD60

TypeSM 234

General information

Note-
Features4 inputs/2 outputs
Configurable
Voltage, current
Resistance, resistance thermometer

Current consumption/power loss

Current consumption from backplane bus100 mA
Power loss2.9 W

Technical data analog inputs

Number of inputs4
Cable length, shielded200 m
Rated load voltageDC 24 V
Reverse polarity protection of rated load voltage
Current consumption from load voltage L+ (without load)70 mA
Voltage inputs
Min. input resistance (voltage range)120 kΩ
Input voltage ranges+1 V ... +5 V
0 V ... +10 V
-10 V ... +10 V
-400 mV ... +400 mV
-4 V ... +4 V
Operational limit of voltage ranges+/-0.3% ... +/-0.7%
Operational limit of voltage ranges with SFU-
Basic error limit voltage ranges+/-0.2% ... +/-0.5%
Basic error limit voltage ranges with SFU-
Destruction limit voltagemax. 15V
Current inputs
Max. input resistance (current range)90 Ω
Input current ranges+4 mA ... +20 mA
0 mA ... +20 mA
-20 mA ... +20 mA
Operational limit of current ranges+/-0.3% ... +/-0.8%
Operational limit of current ranges with SFU-
Basic error limit current ranges+/-0.2% ... +/-0.5%
Radical error limit current ranges with SFU-
Destruction limit current inputs (electrical current)max. 50mA
Destruction limit current inputs (voltage)max. 15V
Resistance inputs
Resistance ranges0 ... 600 Ohm
0 ... 3000 Ohm
Operational limit of resistor ranges+/-0.4%
Operational limit of resistor ranges with SFU-
Basic error limit+/-0.2%
Basic error limit with SFU-
Destruction limit resistance inputsmax. 15V
Resistance thermometer inputs
Resistance thermometer rangesPt100
Pt1000
Ni100
Ni1000
Operational limit of resistance thermometer ranges+/-0.4% ... +/-1.0%
Operational limit of resistance thermometer ranges with SFU-
Basic error limit thermoresistor ranges+/-0.2% ... +/-0.5%
Basic error limit thermoresistor ranges with SFU-
Destruction limit resistance thermometer inputsmax. 15V
Thermocouple inputs-
Thermocouple ranges-
Operational limit of thermocouple ranges-
Operational limit of thermocouple ranges with SFU-
Basic error limit thermoelement ranges-
Basic error limit thermoelement ranges with SFU-
Destruction limit thermocouple inputs-
Programmable temperature compensation-
External temperature compensation-
Internal temperature compensation-
Temperature error internal compensation-
Technical unit of temperature measurement°C
Resolution in bit16
Measurement principleSigma-Delta
Basic conversion time7 ms - 272 ms
Noise suppression for frequency50 Hz and 60 Hz
Initial data size4 Byte

Technical data analog outputs

Number of outputs2
Cable length, shielded200 m
Rated load voltageDC 24 V
Reverse polarity protection of rated load voltage
Current consumption from load voltage L+ (without load)70 mA
Voltage output short-circuit protection
Voltage outputs
Min. load resistance (voltage range)1 kΩ
Max. capacitive load (current range)1 µF
Max. inductive load (current range)30 mA
Output voltage ranges-10 V ... +10 V
+1 V ... +5 V
0 V ... +10 V
Operational limit of voltage ranges+/-0.4% ... +/-0.8%
Basic error limit voltage ranges+/-0.2% ... +/-0.4%
Destruction limit against external applied voltagemax. 15V
Current outputs
Max. in load resistance (current range)500 Ω
Max. inductive load (current range)10 mH
Typ. open circuit voltage current output13 V
Output current ranges-20 mA ... +20 mA
+4 mA ... +20 mA
0 mA ... +20 mA
Operational limit of current ranges+/-0.3% ... +/-0.8%
Basic error limit current ranges+/-0.2% ... +/-0.5%
Destruction limit against external applied voltagemax. 15V
Settling time for ohmic load0.3 ms
Settling time for capacitive load1 ms
Settling time for inductive load0.5 ms
Resolution in bit12
Conversion time1.5 ms/channel
Substitute value can be appliedyes
Output data size4 Byte

Status information, alarms, diagnostics

Status displaynone
Interruptsyes
Process alarmno
Diagnostic interruptyes, parameterizable
Diagnostic functionsyes
Diagnostics information read-outpossible
Supply voltage displaynone
Group error displayred SF LED
Channel error displaynone

Isolation

Between channels-
Between channels of groups to-
Between channels and backplane bus
Between channels and power supply
Max. potential difference between circuits-
Max. potential difference between inputs (Ucm)DC 4 V
Max. potential difference between Mana and Mintern (Uiso)-
Max. potential difference between inputs and Mana (Ucm)-
Max. potential difference between inputs and Mintern (Uiso)DC 75 V/ AC 50 V
Max. potential difference between Mintern and outputs-
Insulation tested withDC 500 V

Datasizes

Input bytes8
Output bytes4
Parameter bytes18
Diagnostic bytes12

Housing

MaterialPPE / PA 6.6
MountingProfile rail 35 mm

Mechanical data

Dimensions (WxHxD)25.4 mm x 76 mm x 88 mm
Weight100 g

Environmental conditions

Operating temperature0 °C to 60 °C
Storage temperature-25 °C to 70 °C

Certifications

UL certificationyes
KC certification-

Downloads

[Datasheet]
[Manual]