231-1BF00 - Signal modules analog | Analog input modules

Order no.

231-1BF00

TypeSM 231

General information

Note-
Features8 inputs
Configurable
Voltage 0...60 mV
Resistance thermometer, thermocouple

Current consumption/power loss

Current consumption from backplane bus280 mA
Power loss1.4 W

Technical data analog inputs

Number of inputs8
Cable length, shielded200 m
Rated load voltage-
Current consumption from load voltage L+ (without load)-
Voltage inputs
Min. input resistance (voltage range)2 MΩ
Input voltage ranges0 mV ... +60 mV
Operational limit of voltage ranges-
Operational limit of voltage ranges with SFU-
Basic error limit voltage ranges+/-0.1%
Basic error limit voltage ranges with SFU-
Destruction limit voltagemax. 15V
Current inputs-
Max. input resistance (current range)-
Input current ranges-
Operational limit of current ranges-
Operational limit of current ranges with SFU-
Grundfehlergrenze Strombereiche-
Radical error limit current ranges with SFU-
Destruction limit current inputs (electrical current)-
Destruction limit current inputs (voltage)-
Resistance inputs-
Resistance ranges-
Operational limit of resistor ranges-
Operational limit of resistor ranges with SFU-
Basic error limit-
Basic error limit with SFU-
Destruction limit resistance inputs-
Resistance thermometer inputs
Resistance thermometer rangesPt100
Operational limit of resistance thermometer ranges-
Operational limit of resistance thermometer ranges with SFU-
Basic error limit thermoresistor ranges±0.15% (2-wire) ±0.15% (4-wire)
Basic error limit thermoresistor ranges with SFU-
Destruction limit resistance thermometer inputsmax. 15V
Thermocouple inputs
Thermocouple rangestype J
type K
type T
Operational limit of thermocouple ranges-
Operational limit of thermocouple ranges with SFU-
Basic error limit thermoelement ranges±0.1% (Compensation external) ±1.0% (internal)
Basic error limit thermoelement ranges with SFU-
Destruction limit thermocouple inputsmax. 15V
Programmable temperature compensation
External temperature compensation
Internal temperature compensation
Temperature error internal compensation4 K
Technical unit of temperature measurement-
Resolution in bit16
Measurement principleSigma-Delta
Basic conversion time6.75 ms ... 268 ms
Noise suppression for frequency50 Hz and 60 Hz
Initial data size16 Byte

Status information, alarms, diagnostics

Status displaynone
Interruptsyes
Process alarmno
Diagnostic interruptyes, parameterizable
Diagnostic functionsyes
Diagnostics information read-outpossible
Supply voltage displaynone
Group error displayred SF LED
Channel error displayred LED per channel

Isolation

Between channels-
Between channels of groups to-
Between channels and backplane bus
Between channels and power supply-
Max. potential difference between circuits-
Max. potential difference between inputs (Ucm)DC 15 V
Max. potential difference between Mana and Mintern (Uiso)-
Max. potential difference between inputs and Mana (Ucm)-
Max. potential difference between inputs and Mintern (Uiso)DC 75 V/ AC 15 V
Max. potential difference between Mintern and outputs-
Insulation tested withDC 500 V

Datasizes

Input bytes16
Output bytes0
Parameter bytes12
Diagnostic bytes12

Housing

MaterialPPE / PA 6.6
MountingProfile rail 35 mm

Mechanical data

Dimensions (WxHxD)25.4 mm x 76 mm x 88 mm
Weight90 g

Environmental conditions

Operating temperature0 °C to 60 °C
Storage temperature-25 °C to 70 °C

Certifications

UL certificationyes
KC certification-

Downloads

[Datasheet]
[Manual]