231-1BD53 - Signal modules analog | Analog input modules

Order no.

231-1BD53

TypeSM 231

General information

Note-
Features4 inputs
Configurable
Voltage, current
Resistance
Resistance thermometer, thermocouple

Current consumption/power loss

Current consumption from backplane bus280 mA
Power loss1.4 W

Technical data analog inputs

Number of inputs4
Cable length, shielded200 m
Rated load voltage-
Current consumption from load voltage L+ (without load)-
Voltage inputs
Min. input resistance (voltage range)20 MΩ
Input voltage ranges-50 mV ... +50 mV
-400 mV ... +400 mV
-4 V ... +4 V
-10 V ... +10 V
Operational limit of voltage ranges+/-0.3% ... +/-0.6%
Operational limit of voltage ranges with SFU-
Basic error limit voltage ranges+/-0.2% ... +/-0.4%
Basic error limit voltage ranges with SFU-
Destruction limit voltagemax. 15V
Current inputs
Max. input resistance (current range)85 Ω
Input current ranges-20 mA ... +20 mA
0 mA ... +20 mA
+4 mA ... +20 mA
Operational limit of current ranges+/-0.3% ... +/-0.8%
Operational limit of current ranges with SFU-
Grundfehlergrenze Strombereiche+/-0.2% ... +/-0.5%
Radical error limit current ranges with SFU-
Destruction limit current inputs (electrical current)max. 30mA
Destruction limit current inputs (voltage)-
Resistance inputs
Resistance ranges0 ... 60 Ohm
0 ... 600 Ohm
0 ... 3000 Ohm
0 ... 6000 Ohm
Operational limit of resistor ranges+/-0.4% ... +/-0.8%
Operational limit of resistor ranges with SFU-
Basic error limit+/-0.2% ... +/-0.4%
Basic error limit with SFU-
Destruction limit resistance inputsmax. 15V
Resistance thermometer inputs
Resistance thermometer rangesPt100, Pt1000
KTY81-152
Ni100, Ni1000
Cu50
KTY81-110
KTY81-120
KTY81-121
KTY81-122
KTY81-150
KTY81-151
Operational limit of resistance thermometer ranges+/-0.4% ... +/-1.4%
Operational limit of resistance thermometer ranges with SFU-
Basic error limit thermoresistor ranges+/-0.2% ... +/-0.7%
Basic error limit thermoresistor ranges with SFU-
Destruction limit resistance thermometer inputsmax. 15V
Thermocouple inputs
Thermocouple rangestype J
type K
type N
type R
type S
type E
type T
Operational limit of thermocouple ranges+/-1.5%
Operational limit of thermocouple ranges with SFU-
Basic error limit thermoelement ranges+/-1.0%
Basic error limit thermoelement ranges with SFU-
Destruction limit thermocouple inputsmax. 15V
Programmable temperature compensation
External temperature compensation
Internal temperature compensation
Temperature error internal compensation5 K
Technical unit of temperature measurement°C
Resolution in bit16
Measurement principleSigma-Delta
Basic conversion time7 ms ... 272 ms
Noise suppression for frequencynone
Initial data size8 Byte

Status information, alarms, diagnostics

Status displaynone
Interruptsyes
Process alarmno
Diagnostic interruptyes, parameterizable
Diagnostic functionsyes
Diagnostics information read-outpossible
Supply voltage displaynone
Group error displaynone
Channel error displayred LED per channel

Isolation

Between channels-
Between channels of groups to-
Between channels and backplane bus
Between channels and power supply-
Max. potential difference between circuits-
Max. potential difference between inputs (Ucm)DC 4 V
Max. potential difference between Mana and Mintern (Uiso)-
Max. potential difference between inputs and Mana (Ucm)-
Max. potential difference between inputs and Mintern (Uiso)DC 75 V/ AC 50 V
Max. potential difference between Mintern and outputs-
Insulation tested withDC 500 V

Datasizes

Input bytes8
Output bytes0
Parameter bytes12
Diagnostic bytes12

Housing

MaterialPPE / PA 6.6
MountingProfile rail 35 mm

Mechanical data

Dimensions (WxHxD)25.4 mm x 76 mm x 88 mm
Weight100 g

Environmental conditions

Operating temperature0 °C to 60 °C
Storage temperature-25 °C to 70 °C

Certifications

UL certificationyes
KC certification-

Downloads

[Datasheet]
[Manual]