231-1BD30 - Signal modules analog | Analog input modules
Order no. |
231-1BD30 |
Type | SM 231, ECO |
General information |
|
Note | - |
Features | 4 inputs Configurable Voltage +/-10 V |
Current consumption/power loss |
|
Current consumption from backplane bus | 120 mA |
Power loss | 0.6 W |
Technical data analog inputs |
|
Number of inputs | 4 |
Cable length, shielded | 200 m |
Rated load voltage | - |
Current consumption from load voltage L+ (without load) | - |
Voltage inputs | |
Min. input resistance (voltage range) | 100 kΩ |
Input voltage ranges | -10 V ... +10 V |
Operational limit of voltage ranges | +/-0.2% |
Operational limit of voltage ranges with SFU | - |
Basic error limit voltage ranges | +/-0.1% |
Basic error limit voltage ranges with SFU | - |
Destruction limit voltage | max. 30V |
Current inputs | - |
Max. input resistance (current range) | - |
Input current ranges | - |
Operational limit of current ranges | - |
Operational limit of current ranges with SFU | - |
Grundfehlergrenze Strombereiche | - |
Radical error limit current ranges with SFU | - |
Destruction limit current inputs (electrical current) | - |
Destruction limit current inputs (voltage) | - |
Resistance inputs | - |
Resistance ranges | - |
Operational limit of resistor ranges | - |
Operational limit of resistor ranges with SFU | - |
Basic error limit | - |
Basic error limit with SFU | - |
Destruction limit resistance inputs | - |
Resistance thermometer inputs | - |
Resistance thermometer ranges | - |
Operational limit of resistance thermometer ranges | - |
Operational limit of resistance thermometer ranges with SFU | - |
Basic error limit thermoresistor ranges | - |
Basic error limit thermoresistor ranges with SFU | - |
Destruction limit resistance thermometer inputs | - |
Thermocouple inputs | - |
Thermocouple ranges | - |
Operational limit of thermocouple ranges | - |
Operational limit of thermocouple ranges with SFU | - |
Basic error limit thermoelement ranges | - |
Basic error limit thermoelement ranges with SFU | - |
Destruction limit thermocouple inputs | - |
Programmable temperature compensation | - |
External temperature compensation | - |
Internal temperature compensation | - |
Temperature error internal compensation | - |
Technical unit of temperature measurement | - |
Resolution in bit | 13 |
Measurement principle | successive approximation |
Basic conversion time | 2 ms / channel |
Noise suppression for frequency | f=50 Hz...400 Hz |
Initial data size | 8 Byte |
Status information, alarms, diagnostics |
|
Status display | none |
Interrupts | no |
Process alarm | no |
Diagnostic interrupt | no |
Diagnostic functions | no |
Diagnostics information read-out | none |
Supply voltage display | none |
Group error display | red SF LED |
Channel error display | none |
Isolation |
|
Between channels | - |
Between channels of groups to | - |
Between channels and backplane bus | |
Between channels and power supply | - |
Max. potential difference between circuits | - |
Max. potential difference between inputs (Ucm) | DC 2 V |
Max. potential difference between Mana and Mintern (Uiso) | - |
Max. potential difference between inputs and Mana (Ucm) | - |
Max. potential difference between inputs and Mintern (Uiso) | DC 75 V/ AC 50 V |
Max. potential difference between Mintern and outputs | - |
Insulation tested with | DC 500 V |
Datasizes |
|
Input bytes | 8 |
Output bytes | 0 |
Parameter bytes | 12 |
Diagnostic bytes | 0 |
Housing |
|
Material | PPE / PA 6.6 |
Mounting | Profile rail 35 mm |
Mechanical data |
|
Dimensions (WxHxD) | 25.4 mm x 76 mm x 88 mm |
Weight | 90 g |
Environmental conditions |
|
Operating temperature | 0 °C to 60 °C |
Storage temperature | -25 °C to 70 °C |
Certifications |
|
UL certification | yes |
KC certification | - |