100V > Moduli digitali

123-4EJ20 - Signal modules digital | Digital in/output modules

Order no.

123-4EJ20

TypeEM 123

General information

Note-
Features16 inputs
AC/DC 60...230 V
8 relay outputs

Current consumption/power loss

Current consumption from backplane bus320 mA
Power loss4.6 W

Technical data digital inputs

Number of inputs16
Cable length, shielded1000 m
Cable length, unshielded600 m
Rated load voltage-
Current consumption from load voltage L+ (without load)-
Rated valueAC/DC 60...230 V
Input voltage for signal "0"AC/DC 0...35 V
Input voltage for signal "1"AC/DC 60...230 V
Input voltage hysteresis-
Frequency range-
Input resistance-
Input current for signal "1"2 mA
Connection of Two-Wire-BEROs possible-
Max. permissible BERO quiescent current-
Input delay of "0" to "1"25 ms
Input delay of "1" to "0"25 ms
Number of simultaneously utilizable inputs horizontal configuration16
Number of simultaneously utilizable inputs vertical configuration16
Input characteristic curve-
Initial data size2 Byte

Technical data digital outputs

Number of outputs8
Cable length, shielded1000 m
Cable length, unshielded600 m
Rated load voltageDC 30 V/ AC 230 V
Reverse polarity protection of rated load voltage-
Current consumption from load voltage L+ (without load)-
Output current at signal "1", rated value5 A
Output delay of "0" to "1"10 ms
Output delay of "1" to "0"5 ms
Minimum load current-
Lamp load-
Parallel switching of outputs for redundant control of a loadnot possible
Parallel switching of outputs for increased powernot possible
Actuation of digital input-
Switching frequency with resistive loadmax. 0.33 Hz
Switching frequency with inductive load-
Switching frequency on lamp load-
Internal limitation of inductive shut-off voltage-
Short-circuit protection of output-
Trigger level-
Number of operating cycle of relay outputs10^7
Switching capacity of contacts-
Output data size1 Byte

Status information, alarms, diagnostics

Status displaygreen LED per channel
Interruptsno
Process alarmno
Diagnostic interruptno
Diagnostic functionsno
Diagnostics information read-outnone
Supply voltage displaynone
Group error displaynone
Channel error displaynone

Isolation

Between channels-
Between channels of groups to8
Between channels and backplane bus
Insulation tested withDC 500 V

Datasizes

Input bytes2
Output bytes2
Parameter bytes0
Diagnostic bytes0

Housing

MaterialPPE / PA 6.6
MountingProfile rail 35 mm

Mechanical data

Dimensions (WxHxD)101.6 mm x 76 mm x 48 mm
Weight244 g

Environmental conditions

Operating temperature0 °C to 60 °C
Storage temperature-25 °C to 70 °C

Certifications

UL certificationyes
KC certification-

Downloads

[Datasheet]
[Manual]